视频1 视频21 视频41 视频61 视频文章1 视频文章21 视频文章41 视频文章61 推荐1 推荐3 推荐5 推荐7 推荐9 推荐11 推荐13 推荐15 推荐17 推荐19 推荐21 推荐23 推荐25 推荐27 推荐29 推荐31 推荐33 推荐35 推荐37 推荐39 推荐41 推荐43 推荐45 推荐47 推荐49 关键词1 关键词101 关键词201 关键词301 关键词401 关键词501 关键词601 关键词701 关键词801 关键词901 关键词1001 关键词1101 关键词1201 关键词1301 关键词1401 关键词1501 关键词1601 关键词1701 关键词1801 关键词1901 视频扩展1 视频扩展6 视频扩展11 视频扩展16 文章1 文章201 文章401 文章601 文章801 文章1001 资讯1 资讯501 资讯1001 资讯1501 标签1 标签501 标签1001 关键词1 关键词501 关键词1001 关键词1501 专题2001
喷淋水力计算
2025-10-02 15:36:25 责编:小OO
文档
计算原理参照《自动喷水灭火系统设计规范GB 50084-2001》(2005年版) 

基本计算公式: 

1、喷头流量: 

                    

   式中:q -- 喷头处节点流量,L/min 

         P -- 喷头处水压(喷头工作压力)MPa

         K -- 喷头流量系数

2、流速V: 

                    

   式中:Q -- 管段流量L/s

         Dj --管道的计算内径(m)

3、水力坡降: 

                    

   式中:i -- 每米管道的水头损失(mH20/m)

         V -- 管道内水的平均流速(m/s)

         dj -- 管道的计算内径(m),取值应按管道的内径减1mm确定

4、沿程水头损失: 

                    

   式中:L -- 管段长度m

5、局部损失(采用当量长度法): 

                     (当量)

   式中:L(当量) -- 管段当量长度,单位m(《自动喷水灭火系统设计规范》附录C)

6、总损失: 

                    

7、终点压力: 

                    

管段名称起点压力mH2O

管道流量L/s

管长m

当量长度管径mm

K水力坡降mH2O/m

流速m/s

损失mH2O

终点压力mH2O

1-27.001.113.100.8025800.5392.092.109.10
2-39.102.383.101.8032800.5302.512.6011.70
3-411.703.811.552.1032801.3654.024.9816.68
30-317.001.113.100.8025800.5392.092.109.10
31-329.102.383.101.8032800.5302.512.6011.70
32-411.703.811.552.1032801.3654.024.9816.68
4-516.687.633.403.6050800.53.594.5121.20
33-348.751.243.100.8025800.6742.342.6311.38
34-3511.382.663.101.8032800.6632.803.2514.63
35-514.634.271.552.3032801.7064.506.5721.19
36-378.751.243.100.8025800.6742.342.6311.38
37-3811.382.663.101.8032800.6632.803.2514.63
38-514.634.271.552.3032801.7064.506.5721.19
5-621.2016.163.404.3065800.7554.585.8127.01
39-4011.161.403.100.8025800.8592.3.3514.51
40-4114.513.003.101.8032800.8453.174.1418.65
41-618.654.821.552.3032802.1755.088.3827.02
42-4311.161.403.100.8025800.8592.3.3514.51
43-4414.513.003.101.8032800.8453.174.1418.65
44-618.654.821.552.3032802.1755.088.3827.02
6-727.0125.793.404.6080800.7775.206.2133.22
7-833.2225.793.400.0080800.7775.202.35.86
8-935.8625.793.400.8080800.7775.203.2639.13
9-1039.1325.793.400.00100800.1782.980.6039.73
10-1139.7325.793.400.00100800.1782.980.6040.34
11-1240.3425.793.400.00100800.1782.980.6040.94
12-1340.9425.793.400.00100800.1782.980.6041.54
13-1441.5425.793.401.10100800.1782.980.8042.34
14-1542.3425.793.400.00125800.0571.940.1942.54
15-1642.5425.793.400.00125800.0571.940.1942.73
16-1742.7325.793.401.30125800.0571.940.2743.00
17-1843.0025.793.400.00150800.0231.370.0843.08
18-1943.0825.793.400.00150800.0231.370.0843.16
19-2043.1625.793.400.00150800.0231.370.0843.23
20-2143.2325.793.400.00150800.0231.370.0843.31
21-2243.3125.793.400.00150800.0231.370.0843.39
22-2343.3925.793.400.00150800.0231.370.0843.46
23-2443.4625.793.400.00150800.0231.370.0843.54
24-2543.5425.793.400.00150800.0231.370.0843.62
25-2643.6225.793.400.00150800.0231.370.0843.69
26-2743.6925.793.400.00150800.0231.370.0843.77
27-2843.7725.793.400.00150800.0231.370.0843.85
28-2943.8525.793.550.00150800.0231.370.0843.93
计算结果:

所选作用面积:161.0平方米

总流量:25.79 L/s

平均喷水强度:9.61 L/min.平方米

入口压力:43.93 米水柱

3、高差计算 

泵房水池吸水管标高为—10米,最高处喷头标高为7.00,高差Z =6+7=17米。

4、主干管沿程损失及局部损失 

自吸水管路至三楼最不利区域入口处管路为DN150,管长为120米。

按流量25.79L/s,计算沿程损失和局部损失共计4米。

5、泵站损失取5米。

6、湿式报警阀及水流指示器水损取6米。

7、喷淋泵扬程

 H=43.93+17+4+5+6=76米。

三、计算结果

1、喷淋泵参数

现选择的喷淋泵参数为流量100m³/h,扬程76米。下载本文