额定
容量
| kVA | 额定 电流 A | 电压组合(kV) | 联结 组别 | 空载电流 % | 空载损耗 A | 负载损耗W (Yyn0/Dyn11) | 阻抗电压 | |
| 高压 | 低压 | |||||||
| 10 | 0.577 14.4 | 6.0 ± 5% 6.3 ± 5% 10 ± 5% | 1.4 | Yyn0 Dyn11 | 1.2 | 55 | 310 | 4.0 |
| 20 | 1.154 28.9 | 1.0 | 70 | 525 | ||||
| 30 | 1.73 43.3 | 0.8 | 100 | 600 | ||||
| 50 | 2. 72.2 | 0.75 | 130 | 870 | ||||
| 63 | 3. 90.9 | 0.70 | 150 | 1040/1120 | ||||
| 80 | 4.62 115.5 | 0.70 | 180 | 1250/1360 | ||||
| 100 | 5.77 144.3 | 0.65 | 200 | 1500/1610 | ||||
| 125 | 7.22 180.4 | 0.65 | 240 | 1800/1870 | ||||
| 160 | 9.24 230.9 | 0.60 | 280 | 2200/2390 | ||||
| 200 | 11.6 288.7 | 0.60 | 340 | 2600/2670 | ||||
| 250 | 14.43 360.8 | 0.50 | 400 | 3050/3130 | ||||
| 315 | 18.19 454.7 | 0.45 | 480 | 3650/3730 | ||||
| 400 | 23.09 577.4 | 0.40 | 570 | 4300/4450 | ||||
| 500 | 28.9 721.7 | 0.40 | 680 | 5100/5290 | ||||
| 630 | 36.4 909 | 0.40 | 810 | 6200/6510 | 4.5 | |||
| 800 | 46.2 1154.7 | 0.40 | 980 | 7500/7850 | ||||
| 1000 | 57.7 1443.4 | 0.30 | 1150 | 10300/10830 | ||||
| 1250 | 72.2 1804.3 | 0.30 | 1360 | 12000/13400 | ||||
| 1600 | 92.4 2309 | 0.30 | 10 | 14500/15210 | ||||
| 2000 | 115.5 2886.7 | 0.30 | 1720 | 17800 | 5.5 | |||
| 2500 | 144.3 3608.4 | 0.30 | 2020 | 20700 | ||||